SmartSlot
Customize UPS capabilities with management cards.
LED status indicators
Quickly understand unit and power status with visual indicators.
Network manageable
Provides remote power management of the UPS over the network.
InfraStruXure Manager Compatib
Enables centralized management via the APC InfraStruXure Manager.
Serial connectivity
Provides management of the UPS via a serial port.
Scalable runtime
Allows additional run time to be quickly added as needed.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Automatic restart of loads after UPS shutdown
Automatically starts up the connected equipment upon the return of utility power.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Avoids costly power problems by keeping your IT equipment and data protected and available.
Network grade power conditioning protects from damaging surges and disruptive noise. The double conversion architecture provides tight voltage regulation, frequency regulation ,and zero transfer time to battery during power events.
Low operating and maintenance costs with proven reliability and intelligent battery management.
Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature compensated charging. Automatic self tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy to connect, hot-swappable battery modules provide battery replacement without powering down.
Save time with easy and convenient remote/network accessibility.
Network manageable via serial, USB or Ethernet. Includes Powerchute® Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.
Peace of mind that comes with full equipment compatibility and reliability of a leader
Provides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.
Resettable circuit breaker
Easy recovery from overloads; no need to replace a fuse.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Cold-start capable
Provides temporary battery power when the utility power is out.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Disconnected battery notification
Warns when a battery is not available to provide backup power.
Audible alarms
Provides notification of changing utility power and UPS power conditions
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Predicitive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
Flash upgradeable firmware
Install maintenance releases of firmware remotely using FTP.
Rack/Tower convertible
Protects the initial investment in the UPS when migrating from tower to rack-mount environment.
Plug-and-Play external batteries
Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
Afghanistan , Antigua and Barbuda , Anguilla , Netherlands Antilles , Argentina , Aruba , Barbados , Bangladesh , Bermuda , Brunei , Bolivia , Bahamas , Bhutan , Belize , Cook Islands , Chile , Colombia , Costa Rica , Cuba , Dominica , Dominican Republic , Ecuador , Fiji , Falkland Islands , Grenada , Guatemala , Guyana , Hong Kong , Honduras , Haiti , Indonesia , Jamaica , Cambodia , Saint Kitts And Nevis , South Korea , Cayman Islands , Saint Lucia , Sri Lanka , Myanmar , Mexico , Malaysia , Nicaragua , Nepal , Panama , Peru , Papua New Guinea , Puerto Rico , Paraguay , Singapore , El Salvador , TP , Trinidad and Tobago , Uruguay , Saint Vincent And The Grenadines , Venezuela , U.S. Virgin Islands , Vietnam
Output
Output power capacity | 8.0 KWatts / 10.0 kVA |
Max Configurable Power (Watts) | 8.0 KWatts / 10.0 kVA |
Nominal Output Voltage | 230V |
Output Voltage Note | Configurable for 220 : 230 or 240 nominal output voltage |
Output Voltage Distortion | Less than 3% |
Output Frequency (sync to mains) | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
Other Output Voltages | 220, 240 |
Load Crest Factor | 3 : 1 |
Topology | Double Conversion Online |
Waveform type | Sine wave |
Output Connections
(8) IEC 320 C13 (Battery Backup)
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
(4) IEC 320 C19 (Battery Backup)
(6) IEC Jumpers (Battery Backup)
Bypass | Internal Bypass (Automatic and Manual) |
Input
Nominal Input Voltage | 230V , 400V 3PH |
Input frequency | 50/60 Hz +/- 5 Hz (auto sensing) |
Input Connections | Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G) |
Input voltage range for main operations | 160 - 280V |
Input Total Harmonic Distortio | Less than 7% for full load |
Other Input Voltages | 220, 240 |
Batteries & Runtime
Battery type | Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof | |
Included Battery Modules | 4 | |
Typical recharge time | 2.2hour(s) | |
Replacement Battery | APCRBC140 | |
Expected Battery Life (years) | 3 - 5 | |
RBC Quantity | 2 | |
Extendable Run Time | 1 | |
Extended Run Options | APC-Smart-UPS-RT-10000VA-230V | |
Runtime | View Runtime Graph | View Runtime Chart |
Efficiency | View Efficiency Graph |
Communications & Management
Interface Port(s) | DB-9 RS-232 , SmartSlot |
Pre-Installed SmartSlot™ Cards | AP9631 |
Control panel | LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
Audible Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
Emergency Power Off (EPO) | Yes |
Surge Protection and Filtering
Surge energy rating | 1265JJoules |
Filtering | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
Physical
Maximum Height | 432mm , 43.2CM |
Maximum Width | 263mm , 26.3CM |
Maximum Depth | 736mm , 73.6CM |
Rack Height | 6U |
Net Weight | 110.91KG |
Shipping weight | 129.09KG |
Shipping Height | 552mm , 55.2CM |
Shipping Width | 597mm , 59.7CM |
Shipping Depth | 991mm , 99.1CM |
Color | Black |
Units per Pallet | 2.0 |
Environmental
Operating Temperature | 0 - 40 °C |
Operating Relative Humidity | 0 - 95% non-condensing % |
Operating Elevation | 0-3000meters |
Storage Temperature | -15 - 45 °C |
Storage Relative Humidity | 0 - 95% non-condensing % |
Storage Elevation | 0-15000meters |
Audible noise at 1 meter from surface of unit | 55.0dBA |
Online thermal dissipation | 2262.0BTU/hr |
Protection Class | IP 20 |
Conformance
Approvals | C-tick, CE, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, GOST, VDE |
Sustainable Offer Status
RoHS | Compliant |
PEP | Available in Documentation tab |
EOLI | Available in Documentation tab |
Other Environmental Compliance | China RoHS |