+964 750 905 1010
info [at] helptechco [dot] com
B2B

  • 6U
  • 10000VA
  • Smart-UPS
  • SURT10000XLI

Smart-UPS On-Line Features & Benefits
​Manageability

SmartSlot

Customize UPS capabilities with management cards.

LED status indicators

Quickly understand unit and power status with visual indicators.

Network manageable

Provides remote power management of the UPS over the network.

InfraStruXure Manager Compatib

Enables centralized management via the APC InfraStruXure Manager.

Serial connectivity

Provides management of the UPS via a serial port.

Availability

Scalable runtime

Allows additional run time to be quickly added as needed.

Intelligent battery management

Maximizes battery performance, life, and reliability through intelligent, precision charging.

Automatic internal bypass

Supplies utility power to the connected loads in the event of a UPS power overload or fault.

Automatic restart of loads after UPS shutdown

Automatically starts up the connected equipment upon the return of utility power.

Temperature-compensated battery charging

Prolongs battery life by regulating the charge voltage according to battery temperature.

Hot-swappable batteries

Ensures clean, uninterrupted power to protected equipment while batteries are being replaced

Marketing Features

Avoids costly power problems by keeping your IT equipment and data protected and available.

Network grade power conditioning protects from damaging surges and disruptive noise. The double conversion architecture provides tight voltage regulation, frequency regulation ,and zero transfer time to battery during power events.

Low operating and maintenance costs with proven reliability and intelligent battery management.

Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature compensated charging. Automatic self tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy to connect, hot-swappable battery modules provide battery replacement without powering down.

Save time with easy and convenient remote/network accessibility.

Network manageable via serial, USB or Ethernet. Includes Powerchute® Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.

Peace of mind that comes with full equipment compatibility and reliability of a leader

Provides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.

Protection

Resettable circuit breaker

Easy recovery from overloads; no need to replace a fuse.

Frequency and voltage regulation

Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.

Safety-agency approved

Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.

Power conditioning

Protects connected loads from surges, spikes, lightning, and other power disturbances.

Generator compatible

Ensures clean, uninterrupted power to protected equipment when generator power is used.

Cold-start capable

Provides temporary battery power when the utility power is out.

Input power factor correction

Minimizes installation costs by enabling the use of smaller generators and cabling.

Serviceability

Disconnected battery notification

Warns when a battery is not available to provide backup power.

Audible alarms

Provides notification of changing utility power and UPS power conditions

User-replaceable batteries

Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)

Automatic self-test

Periodic battery self-test ensures early detection of a battery that needs to be replaced.

Predicitive failure notification

Provides early-warning fault analysis ensuring proactive component replacement.

Adaptability

Flash upgradeable firmware

Install maintenance releases of firmware remotely using FTP.

Rack/Tower convertible

Protects the initial investment in the UPS when migrating from tower to rack-mount environment.

Plug-and-Play external batteries

Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.

Product Distribution

Afghanistan , Antigua and Barbuda , Anguilla , Netherlands Antilles , Argentina , Aruba , Barbados , Bangladesh , Bermuda , Brunei , Bolivia , Bahamas , Bhutan , Belize , Cook Islands , Chile , Colombia , Costa Rica , Cuba , Dominica , Dominican Republic , Ecuador , Fiji , Falkland Islands , Grenada , Guatemala , Guyana , Hong Kong , Honduras , Haiti , Indonesia , Jamaica , Cambodia , Saint Kitts And Nevis , South Korea , Cayman Islands , Saint Lucia , Sri Lanka , Myanmar , Mexico , Malaysia , Nicaragua , Nepal , Panama , Peru , Papua New Guinea , Puerto Rico , Paraguay , Singapore , El Salvador , TP , Trinidad and Tobago , Uruguay , Saint Vincent And The Grenadines , Venezuela , U.S. Virgin Islands , Vietnam

SURT10000XLI
/ /
APC
/

Output

Output power capacity 8.0 KWatts / 10.0 kVA
Max Configurable Power (Watts) 8.0 KWatts / 10.0 kVA
Nominal Output Voltage 230V
Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Other Output Voltages 220, 240
Load Crest Factor 3 : 1
Topology Double Conversion Online
Waveform type Sine wave

Output Connections

(8) IEC 320 C13 (Battery Backup)
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
(4) IEC 320 C19 (Battery Backup)

(6) IEC Jumpers (Battery Backup)

Bypass Internal Bypass (Automatic and Manual)

Input

Nominal Input Voltage 230V , 400V 3PH
Input frequency 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 160 - 280V
Input Total Harmonic Distortio Less than 7% for full load
Other Input Voltages 220, 240

Batteries & Runtime

Battery type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules 4
Typical recharge time 2.2hour(s)
Replacement Battery APCRBC140
Expected Battery Life (years) 3 - 5
RBC Quantity 2
Extendable Run Time 1
Extended Run Options APC-Smart-UPS-RT-10000VA-230V
Runtime View Runtime Graph View Runtime Chart
Efficiency View Efficiency Graph

Communications & Management

Interface Port(s) DB-9 RS-232 , SmartSlot
Pre-Installed SmartSlot™ Cards AP9631
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators
Audible Alarm Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Emergency Power Off (EPO) Yes

Surge Protection and Filtering

Surge energy rating 1265JJoules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height 432mm , 43.2CM
Maximum Width 263mm , 26.3CM
Maximum Depth 736mm , 73.6CM
Rack Height 6U
Net Weight 110.91KG
Shipping weight 129.09KG
Shipping Height 552mm , 55.2CM
Shipping Width 597mm , 59.7CM
Shipping Depth 991mm , 99.1CM
Color Black
Units per Pallet 2.0

Environmental

Operating Temperature 0 - 40 °C
Operating Relative Humidity 0 - 95% non-condensing %
Operating Elevation 0-3000meters
Storage Temperature -15 - 45 °C
Storage Relative Humidity 0 - 95% non-condensing %
Storage Elevation 0-15000meters
Audible noise at 1 meter from surface of unit 55.0dBA
Online thermal dissipation 2262.0BTU/hr
Protection Class IP 20

Conformance

Approvals C-tick, CE, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, GOST, VDE

Sustainable Offer Status

RoHS Compliant
PEP Available in Documentation tab
EOLI Available in Documentation tab
Other Environmental Compliance China RoHS
SURT10000XLI
/ /
APC
/
Top