| Model | Power Solid 1KVa | |
| Capacity (Va/Watt) | 1000 VA / 800 Watt | |
| Input | ||
| Voltage Range | Low Line Transfer | 160VAC/140VAC/120VAC/110VAC ± 5% (Ambient Temp.<35'C) I based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
| Low Line Comeback | 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temp.<35'C)I based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) | |
| High Line Transfer | 300 VAC±5 % | |
| High Line Comeback | 290 VAC ± 5 % | |
| Frequency Range | 40Hz - 70 Hz | |
| Phase | Single phase neutral and ground | |
| Power Factor | ≥ 0.99 @ nominal voltage (input voltage) | |
| Output | ||
| Output Voltage | 200 / 208 / 220 / 230 / 240 VAC (Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 200/208VAC) | |
| AC Voltage Regulation | ±1% | |
| Frequency Range | 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) | |
| Frequency Range (Batt. Model) | 50 Hz± 0.25 Hz or 60Hz ± 0.3 Hz | |
| Overload |
AmbientTemp.<35°( 105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal Overload 110%~130%: UPS shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal ≥ 130%:UPS shuts down after 3 seconds at batter mode or transfer to b p_a_ss when the utilit is r,ormal |
|
| Current Crest Ratio | 3:1 | |
| Harmonic Distortion | ≤ 3 % THD (linear load); ≤ 6 % THD (non-linear load) | |
| Transfer Time | AC to Battery | Zero |
| Inverter to Bypass | 4 ms (Typical) | |
| Waveform | Pure Sinewave | |
| Efficiency | ||
| AC Mode | 88 % | |
| Battery Mode | 83 % | |
| Battery | ||
| Standard Model | Battery Type | 12V /9AH |
| Numbers | 2 | |
| Recharge Time | 4 hours recover to 90% capacity (Typical) | |
| Charging Current | 1.0 A (max.) | |
| Charging Voltage | 27.4 VDC ± 1% | |
| Long-run Model | Battery Numbers | 2 |
| Charging Current | 1.0A / 2.0A / 4.0A / 6.0 A (Adjustable) | |
| Charging Voltage | 27.4 VDC ± 1% | |
| Physical | ||
| Standard Model with Bat. | Dimension, D x W x H | 282 x 145 x 220 (mm) |
| Net Weight (kgs) | 9.8 | |
| Long-run Model | Dimension, DX W X H | 282 x 145 x 220 (mm) |
| Net Weight (kgs) | 4.1 | |
| Environment | ||
| Opeation Humidity | 20-90 % RH @ 0-40°C (non-condensing) | |
| Noise Level | Less than 50dBA @ 1 Meter | |
| Management | ||
| Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8,Linux, Unix and MAC | |
| Optional SNMP | Power management from SNMP manager and web browser | |