Model | Power Solid 2KVa | |
Capacity (Va/Watt) | 2000 VA / 1600 Watt | |
Input | ||
Voltage Range | Low Line Transfer | 160VAC/140VAC/120VAC/110VAC ± 5% (Ambient Temp.<35'C) I based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
Low Line Comeback | 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temp.<35'C)I based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) | |
High Line Transfer | 300 VAC±5 % | |
High Line Comeback | 290 VAC ± 5 % | |
Frequency Range | 40Hz ~ 70 Hz | |
Phase | Single phase neutral and ground | |
Power Factor | ≥ 0.99 @ nominal voltage (input voltage) | |
Output | ||
Output Voltage | 200 / 208 / 220 / 230 / 240 VAC (Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 200/208VAC) | |
AC Voltage Regulation | ±1% | |
Frequency Range | 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) | |
Frequency Range (Batt. Model) | 50 Hz± 0.25 Hz or 60Hz ± 0.3 Hz | |
Overload |
AmbientTemp.<35°( 105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal Overload 110%~130%: UPS shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal ≥ 130%:UPS shuts down after 3 seconds at batter mode or transfer to b p_a_ss when the utilit is r,ormal |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≤ 3 % THD (linear load); ≤ 6 % THD (non-linear load) | |
Transfer Time | AC to Battery | Zero |
Inverter to Bypass | 4 ms (Typical) | |
Waveform | Pure Sinewave | |
Efficiency | ||
AC Mode | 89 % | |
Battery Mode | 87 % | |
Battery | ||
Standard Model | Battery Type | 12V / 9AH |
Numbers | 4 | |
Recharge Time | 4 hours recover to 90% capacity (Typical) | |
Charging Current | 1.0 A (max.) | |
Charging Voltage | 54.7 VDC ±1% | |
Long-run Model | Battery Numbers | 4 |
Charging Current | 1.0A / 2.0A / 4.0A / 6.0 A (Adjustable) | |
Charging Voltage | 54.7 VDC ±1% | |
Physical | ||
Standard Model with Bat. | Dimension, D x W x H | 397 x 145 x 220 (mm) |
Net Weight (kgs) | 17 | |
Long-run Model | Dimension, DX W X H | 397 x 145 x 220 (mm) |
Net Weight (kgs) | 6.8 | |
Environment | ||
Opeation Humidity | 20-90 % RH @ 0-40°C (non-condensing) | |
Noise Level | Less than 50dBA @ 1 Meter | |
Management | ||
Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8,Linux, Unix and MAC | |
Optional SNMP | Power management from SNMP manager and web browser |